3 Phase Isolation Transformer

Primary Voltage: 480V

Secondary Voltage: 208Y/120V

Power Rating: 10 ~ 2000 KVA or customize

Connection Type: Dyn11 (Delta-Primary, Wye-Secondary with neutral), or other configurations

Transformer Type: Dry Type Isolation Transformer

Standards: ANSI/IEEE, CSA/CAN, DOE

Certificates: UL, cUL, CSA, SGS, CE

Product Introduction

Three-phase isolation transformers are essentially a type of isolation transformer. Compared with single-phase transformers, they not only protect sensitive equipment and block voltage spikes, harmonics, and transient surges from the power grid, but also provide higher transmission efficiency and lower losses.

Due to the fact that both the input and output of three-phase isolation transformers are three-phase AC power, they feature larger capacity and higher efficiency. Generally, the output power of three-phase isolation transformers is above 7 kW.

Product Features

Isolation transformers were first used in Europe. What are the differences between isolation transformers and other types of transformers?

Comparison of the Core Differences Between Conventional Transformers and Isolation Transformers

Differences in Additional Functions

Conventional Transformers

  • Designed primarily with power transmission efficiency and capacity matching as the main objectives.
  • Meet the requirements of conventional power distribution systems and adopt basic insulation designs.
  • Focus more on power system transmission efficiency, with limited capability to suppress grid harmonics and electromagnetic interference.

Isolation Transformers

  • Provide excellent noise filtering performance and can eliminate common-mode interference.
  • Effectively block current interference caused by ground loops.
  • Some high-end models are equipped with electrostatic shielding layers to improve EMC performance.

Product Application Scenarios

CHBEB Group specializes in transformer manufacturing and has more than 60 years of experience. From Beijing to Zhejiang, we have grown alongside the development of China’s manufacturing industry. Our isolation transformers are widely used around the world.

From the development of cities across China’s 31 provinces, from north to south, to urban construction projects in Vietnam, Pakistan, Kyrgyzstan, the UAE, and Saudi Arabia, CHBEB products can be found in many applications.

Three-phase isolation transformers are widely used in industrial automation, precision machining, imported and exported equipment, laboratories, and other fields.

Three-Phase Isolation Transformer Electrical Parameters

Item Common Parameters
Type Three-Phase Epoxy Resin Cast Dry-Type Transformer
Energy Efficiency Class NX1 / Class 1 Energy Efficiency
Rated Capacity 30kVA – 2500kVA common; customizable per project
Rated Frequency 50 Hz / 60 Hz
Primary Rated Voltage 6kV / 10kV / 10.5kV / 11kV etc.
Secondary Rated Voltage 0.4kV / 0.415kV / 0.69kV etc.
Common Voltage Ratio 10/0.4kV
Tap Changer Type Off-circuit (no-excitation) tap changing
Tap Range ±2×2.5% or ±5%
Vector Group Dyn11 most common; Yyn0, Yd11 also available
Insulation Class Class F / Class H
Cooling Method AN natural air cooling; AF forced air cooling optional
Protection Rating IP00 / IP20 / IP23 / IP30 / IP40 etc.
Impedance Voltage Approx. 4%–6%, varies with capacity
No-load Current Typically approx. 0.5%–1.5%
Noise Level Approx. 45–60 dB, varies with capacity
Operating Environment Indoor; altitude ≤1000m standard; derating required above 1000m
Applicable Scenarios Distribution rooms, commercial complexes, factories, schools, hospitals, data centers etc.

Ask For A Quick Quote

We will reply to you within 1–2 business days.Please pay attention to the email with the suffix”@chbebpower.com”.