45 kva Isolation Transformer

Primary Voltage: 480V

Secondary Voltage: 480Y/277V

Rated Capacity: 45kVA, customizable

Connection Group: Dyn11 (Delta primary, Wye secondary with neutral); other wiring configurations available

Transformer Type: Isolation Transformer

Standards: ANSI/IEEE, CSA/CAN, U.S. DOE Energy Efficiency Standards

Certifications: UL, cUL, CSA, SGS, CE

Product Advantages of Isolation Transformer

Differences Between Isolation Transformers and Ordinary Transformers

Ordinary Transformer

  • The winding layout is compact and the structure is simple.
  • Parasitic capacitance exists between windings.
  • High-frequency interference may be coupled to the secondary side through capacitance.

Isolation Transformer

  • Adopts a primary and secondary winding partition structure or shielded winding structure.
  • It can effectively reduce the parasitic capacitance between windings.
  • Adopts a multiple insulation structure, providing higher safety.

Application Scenarios of Isolation Transformers

Differences in Application Scenarios Between Isolation Transformers and Ordinary Transformers

Ordinary Transformer

  • Residential distribution systems and industrial plant power supply networks
  • Power conversion modules inside household appliances

Isolation Transformer

  • Power supply systems for medical diagnostic equipment, such as CT machines and monitors
  • Electrical equipment in high-humidity environments, such as bathrooms and swimming pools
  • Dedicated safety power supply for electronic equipment maintenance

45 KVA Isolation Transformer Technical Parameters

Parameter Item Recommended Value
Product Type Three-Phase Dry-Type Isolation Transformer
Rated Capacity 45 kVA
Input Voltage 480V AC
Output Voltage 480V AC
Voltage Ratio 1:1
Phase Three Phase
Rated Frequency 50 / 60 Hz
Primary Rated Current Approx. 54.1A
Secondary Rated Current Approx. 54.1A
Winding Structure Independent primary and secondary windings with galvanic isolation
Recommended Connection Dd0; Dyn11 or Yyn0 available on request
Neutral Line Optional; X0 can be brought out when star output is used
Input Voltage Tap ±2×2.5%: 456V / 468V / 480V / 492V / 504V
Impedance Voltage Approx. 4%, designable from 4%–6%
No-load Current ≤3%
Voltage Regulation Rate ≤3%–5%
Efficiency ≥97% recommended
Winding Material Copper winding preferred; aluminum winding optional
Insulation Class Class H
Temperature Rise Limit 115K or 125K
Cooling Method AN, Natural Air Cooling
Duty Cycle Continuous duty
Electrostatic Shield Electrostatic shielding layer between primary and secondary windings
Insulation Resistance ≥100MΩ between windings and winding-to-ground
Power Frequency Withstand Voltage Primary to secondary and ground: 3kV/1min; subject to certification standards
Protection Rating Indoor IP23/NEMA 1; Outdoor IP54/NEMA 3R
Ambient Temperature Standard -20°C to +40°C; Middle East version designable up to +50°C
Altitude ≤1000m; derating or special design required above 1000m
Grounding Enclosure protective grounding; electrostatic shield separately grounded
Applicable Standards IEC 60076-1, IEC 60076-11, IEC 61558; UL 1561, CSA C22.2 No.47 optional

Ask For A Quick Quote